본문 바로가기 네비게이션 바로가기

Energy saving professional company

Energy saving professional company, Air, Water, Earth, Solar, You can get energy if you meet Iljin E-Plus.

HOME > Products > Air Source Heat Pump (IACH-16B,IACHK-16C series)

Air Source Heat Pump (IACH-16B, IACHK-16C series)

Air Source Heat Pump (IACH-16B, IACHK-16C series)
  • * Product Overview
  • A system that utilizes the external air for the heat pump to provide heating and hot water
  • * Features
  • ① A simple system without the need for a device for waste
        heat collection
    ② As this system can store hot water in the thermal storage
        tank, it can be used not only for cooling but also for heating
        in winter.
    ③ Unlike an ice thermal storage system, this system is
        environment-friendly without using a separate low-
        temperature solution (brine).
    ④ As this system is simple, it is easy to automatically control
        and operate it.
  • * Application
  • Building cooling / heating or hot water
    (all places needing hot water and heating)

* Specification of Air Source Heat Pump (IAVH- 16B, IACK-16C series)


Model
IACH-16B-10
IACH-16B-13
IACH-16B-21
IACH-16B-28
IACHK-16C-39
Capacity
Heating
KW
36.16
45.7
71.44
96.74
137.21
Kcal/h
31,100
39,300
62,300
83,200
118,000
USRT
10.28
13
20.6
27.51
39.02
Cooling
KW
34.77
42.21
69.65
88.37
122.09
Kcal/h
29,900
36,300
59,900
76,000
105,000
USRT
9.89
12
19.81
25.13
34.72
Power Supply
Heat/Cool
KW
13.5/12.9
17.0/16.2
25.3/24.8
37.4/36.2
60.0/55.0
Power Supply
3Phase x 380V x 60Hz
Dimension
Length
mm
2,040
2,380
2,334
3,480
2,680
Height
1,270
1,370
1,600
2,000
2,290
Depth
710
730
1,110
1,110
2,030
Compressor
Type
Scroll type
Screw
Quantity
1
2
1
Operation Method
Direct-on-line
Y-
Volume Control
%
0~100%
Refrigeration Ton
RT
4.12
4.92
8.24
12.35
17.35
Refrigerant
Type
R-22
R-407C
Control Method
Thermostatic expansion valve
Condenser
& Evaporator
Type
Brazed Plate type
Heating
Circulation
Volume
LPM
104
131
208
277
393
Cooling
Circulation
Volume
100
121
200
253
350
Piping(IN/OUT)
A
25
25
40
50
65
Outdoor unit
Type
Finned Copper Tube Type
Thermal Storage Area
m2
108.5
128.2
186.5
330.3
522.6
Fan & Motor
Air
Volume
m3/min
190
240
510
680
1,080
Size
Ø
450x3
500x3
630x3
630x4
700x6
Control
Temperature Control
4 way proportional control valve
Operation Control
PCB
Defrosting
Hot Gas
Reverse Cycle
Weight
kg
400
550
700
800
1200
Conditions for the products
heating
Outdoor (DB7°C); Temp of water supply to be 40°C; Temp of output water to be 45°C;
cooling
Outdoor (DB25°C); Temp of water supply to be 12°C; Temp of output water to be 70°C;

■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.

Air Source Heat Pump | Energy saving system | Ground Source Heat Pump | Heat Pump | Heating Ventilating Air conditioning | Refrigeration System | Sea Water Source Heat Pump | Eco Friendly Heat Pump | Sea Water Source Heat Pump | Air source Heat Pump water Heater | Sitemap.xml