HOME > Products > Air Source Heat Pump (IACH-16B,IACHK-16C series)

* Specification of Air Source Heat Pump (IAVH- 16B, IACK-16C series)
|
Model
|
IACH-16B-10
|
IACH-16B-13
|
IACH-16B-21
|
IACH-16B-28
|
IACHK-16C-39
|
|||
|
Capacity
|
Heating
|
KW
|
36.16
|
45.7
|
71.44
|
96.74
|
137.21
|
|
|
Kcal/h
|
31,100
|
39,300
|
62,300
|
83,200
|
118,000
|
|||
|
USRT
|
10.28
|
13
|
20.6
|
27.51
|
39.02
|
|||
|
Cooling
|
KW
|
34.77
|
42.21
|
69.65
|
88.37
|
122.09
|
||
|
Kcal/h
|
29,900
|
36,300
|
59,900
|
76,000
|
105,000
|
|||
|
USRT
|
9.89
|
12
|
19.81
|
25.13
|
34.72
|
|||
|
Power Supply
|
Heat/Cool
|
KW
|
13.5/12.9
|
17.0/16.2
|
25.3/24.8
|
37.4/36.2
|
60.0/55.0
|
|
|
Power Supply
|
3Phase x 380V x 60Hz
|
|||||||
|
Dimension
|
Length
|
mm
|
2,040
|
2,380
|
2,334
|
3,480
|
2,680
|
|
|
Height
|
1,270
|
1,370
|
1,600
|
2,000
|
2,290
|
|||
|
Depth
|
710
|
730
|
1,110
|
1,110
|
2,030
|
|||
|
Compressor
|
Type
|
Scroll type
|
Screw
|
|||||
|
Quantity
|
1
|
2
|
1
|
|||||
|
Operation Method
|
Direct-on-line
|
Y-
|
||||||
|
Volume Control
|
%
|
0~100%
|
||||||
|
Refrigeration Ton
|
RT
|
4.12
|
4.92
|
8.24
|
12.35
|
17.35
|
||
|
Refrigerant
|
Type
|
R-22
|
R-407C
|
|||||
|
Control Method
|
Thermostatic expansion valve
|
|||||||
|
Condenser
& Evaporator
|
Type
|
Brazed Plate type
|
||||||
|
Heating
Circulation Volume |
LPM
|
104
|
131
|
208
|
277
|
393
|
||
|
Cooling
Circulation Volume |
100
|
121
|
200
|
253
|
350
|
|||
|
Piping(IN/OUT)
|
A
|
25
|
25
|
40
|
50
|
65
|
||
|
Outdoor unit
|
Type
|
Finned Copper Tube Type
|
||||||
|
Thermal Storage Area
|
m2
|
108.5
|
128.2
|
186.5
|
330.3
|
522.6
|
||
|
Fan & Motor
|
Air
Volume |
m3/min
|
190
|
240
|
510
|
680
|
1,080
|
|
|
Size
|
Ø
|
450x3
|
500x3
|
630x3
|
630x4
|
700x6
|
||
|
Control
|
Temperature Control
|
4 way proportional control valve
|
||||||
|
Operation Control
|
PCB
|
|||||||
|
Defrosting
|
Hot Gas
|
Reverse Cycle
|
||||||
|
Weight
|
kg
|
400
|
550
|
700
|
800
|
1200
|
||
|
Conditions for the products
|
heating
|
Outdoor (DB7°C); Temp of water supply to be 40°C; Temp of output water to be 45°C;
|
||||||
|
cooling
|
Outdoor (DB25°C); Temp of water supply to be 12°C; Temp of output water to be 70°C;
|
|||||||
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.